IU2050NC
2000 Series IO Unit 1 In
- Loop powered
- Programmable input state
- Easy numeric addressing
- EN54 approved and CPR certified
Alternatieve producten
Gerelateerde producten
Overzicht
General
The IU2050NC is a 2000 series addressable single input unit with selectable line supervision to monitor normally open or normally closed contacts. The unit is loop powered and supplied in an enclosure for surface mounting applications.
The 2000 series loop powered input/output modules are designed to provide much needed flexibility to input monitoring and output switching. These modules, combined with the powerful features of the Aritech addressable fire panels, give the user versatility for diverse applications.
The 2000 series loop powered input/output modules are designed to provide much needed flexibility to input monitoring and output switching. These modules, combined with the powerful features of the Aritech addressable fire panels, give the user versatility for diverse applications.
Applications
The addressability of the IU2050NC allows the identification of the exact location of the switch activation. It may be used with applications requiring fast response such a conventional manual call points, door monitors etc. where a change of state needs to be reported within 3 seconds. Alternatively it can be used in any application where a point needs to be made addressable and supervised on the fire panel.
Installation
The IU2050NC is connected to and Aritech CIE via a two-wire communication loop that provides power and control data. The single input module address is conveniently set with rotary switches. The address setting is non-volatile and will not be lost in the event of a power failure.
The single input module utilizes an advanced digital data communications protocol that ensures the integrity of the data communications with extensive error correction algorithms.
The single input module utilizes an advanced digital data communications protocol that ensures the integrity of the data communications with extensive error correction algorithms.
Details
- Loop powered
- Programmable input state
- Easy numeric addressing
- EN54 approved and CPR certified
Technische specificaties
| General | ||
|---|---|---|
| Compatibility |
2000 Series Systems
|
|
| Addressing method |
Rotary switch
|
|
| Electrical | ||
|---|---|---|
| Operating voltage |
17 to 28 VDC
|
|
| Current consumption |
<205 μA (Quiescent)
<270 μA (Active)
|
|
| Communication voltage |
4 to 10 V
|
|
| Input | ||
|---|---|---|
| Input quantity |
1
|
|
| Input type and rating |
Supervised
|
|
| Termination resistor |
150 kΩ, ¼ W, 5%
|
|
| Physical | ||
|---|---|---|
| Physical dimensions |
120 x 90 x 35 mm
|
|
| Net weight |
144 g
|
|
| Colour |
Koel grijs
|
|
| Mounting type |
Oppervlaktemontage
|
|
| Cable entries |
1
|
|
| Material |
Plastic
|
|
| Environmental | ||
|---|---|---|
| Vandal proof |
No
|
|
| Operating temperature |
-10 to +55°C
|
|
| Storage temperature |
-20 to +60°C
|
|
| Relative humidity |
10 to 95% noncondensing
|
|
| Environment |
Indendør
|
|
| IP rating |
IP40
|
|
| Regulatory | ||
|---|---|---|
| Compliancy |
CE
REACH
RoHS 2
|
|
| Certification |
BOSEC
VdS
|
|
| Standards |
EN54-18
|
|
Compatibele producten
| Categorie | Referentie | Beschrijving |
|---|---|---|
| Detection device | ISM-95 | 2000/900 Series Stand Alone Loop Isolator (CPD Certified) |
| Interface unit | IO2034NC | 2000 Series IO Unit 4 In / 4 Out |
| Interface unit | IU2055NC | Grenzwerttechnikmodul der 2000er Serie, inkl. Gehäuse |
| Interface unit | IU2080NC | Signalgebermodul der 2000er Serie, inkl. Gehäuse |
Downloads
All downloadsGegevensblad
Installatie fiche
Certificaten
Overig EU certificaat
Overig EU certificaat
VMC_B-9212-FD-K1071-a_IU2050NC, IU2080NC
Overig EU certificaat
VMC_B-9212-FD-1088-b_2X-A series
Indien beschikbaar worden de downloads van de Certificaten, Software & Firmware en Media weergegeven in hun standaardtaal.